AM600
600 kW of natural-gas power in one 20 ft high-cube container: two 300 kW engine-generator modules, factory-tested before shipment. The first unit has rolled off the production line.
Tested in the factory, before it ships.
The first AM600 completed its factory acceptance test on 26 August 2026. Customers can review the unit, test evidence and controlled documents online through CIMC's virtual FAT.
FAT checks recorded
- Gas leak test and emergency shutdown inspection passed
- Overspeed, temperature, oil-pressure and overload protection checks passed
- 0 → 50% sudden loading and 100% → 0 sudden unloading
- Concurrent operation of both modules at full load
Virtual FAT evidence package
7 video records, 12 inspection photos and 14 controlled FAT documents, closed with an electronic acceptance certificate.
Plug-and-play, honestly defined
The package keeps the generation block compact. Site work still includes foundations and unloading, fuel connections, cables and switchgear interfaces, ventilation clearances, permits and commissioning.
Gas delivered by road. Power generated on site.
Where there is no pipeline or the grid is weak, LNG or CNG can be delivered by truck, stored and regasified at the site, then converted to electricity in containerized gas power modules. The 20 ft AM600 and 10 ft SL500 are sized for exactly this end of the chain.
Continuous power from 600 kW blocks.
AM600 and SL500 platforms can be paralleled and scaled from multi-MW deployments up to around 100 MW for continuous power applications such as data centers, mines and industrial sites.
Data centers
Modular gas power blocks for continuous data-center loads, paired with SL500 units.
Data center power →Mines and oilfields
Containerized generation for remote sites, including conditioned associated gas.
Mining power →Technical specifications.
Figures from the AM600 factory record (FAT, 26 August 2026). Fuel version, rated duty, ambient conditions and gas quality decide the project data sheet and site output; hot-climate derating, cooling and enclosure design are calculated for the actual site.
| Parameter | Value |
|---|---|
| Model | AM600 modular natural-gas generator set |
| Package | Single 20 ft high-cube ISO container package |
| Rated output | 600 kW · 400 V · 50 Hz (factory-tested build) |
| Configuration | 2 × 300 kW gas engine-generator modules |
| Fuel | Natural gas (associated gas after conditioning) |
| Rated gas volume | 170 Nm³/h |
| Enclosure protection | IP54 |
| Dimensions (L × W × H) | 6058 × 2438 × 2896 mm |
| Controls | Dual genset controllers; remote monitoring, control and alarm records |
| Other grids | 60 Hz and 380–480 V configurations engineered per project and confirmed in the quotation |
| Scalability | Multi-MW up to around 100 MW (in parallel with SL500 / AM platforms) |
See also the AM600 and AM1200 product-route overview. Final values are stated in the project proposal.
Build the fleet with both formats.
AM600 and SL500 platforms can be paralleled and scaled from multi-MW deployments up to around 100 MW for continuous power applications such as data centers, mines and industrial sites.
SL500 Power Cube · 10 ft · 500 kW
The compact 10 ft partner: 500 kW natural-gas module, 400/480 V, 50/60 Hz, N+1 parallel, ~2 h deployment.
View the SL500 product page →Configure an AM600 for your site.
Send the country, load profile, gas analysis and supply conditions, voltage and frequency, ambient conditions, operating hours and required supply scope.